Characteristics: A mixed inorganic material for sealing off the
large, medium and small-sized penetration holes, with a maximum
fireproof effective time of 4 hours. Application scope for sealing:
cables and cable bridges; wind pipes and metallic pipes. Advantages: Applicable to follow-up application or smearing. No shrinkage
during hardening or burning with fire.No ashestos.halogen and
phenol in its content. No volatile organic solvent in its content. Smoke-proof, gas-proof and waterproof. High performance in
anti-explosion.Pressure bearing up to 2.0bar (200kpa). Fine
insulation. With a fireproof life of 30 years.No need to replace it
within this period. Base materials for it: conerete, bricks,
stones, metals and glass.Thickness of wall not less than
150mm..Thickness of floor not less than 100mm. Technical Index: Under 23℃ temperature and 50% relative humidity Color | Grey | Density (after solidification) | About 0.85g/cm | Mixture ratio | 3:1 (plaster: water) | Temperature for operation | 5℃-40℃(ideal temperature) | Time for removal of formwork (varying with thickness of the mixture) | 2-4 hours (wall). 2-12 hours (floor) |
Installation Instructions: Preparation: 1.Clear off dust and greasy dirt, etc. on the areas around the
openings, cables and cable bridges. Then wet the surface of the
said areas with wate 2. Pour 1 shares water into a container, then add 3 shares FC-1
powder in it.agitate the mixture evenly, making a thick and sticky
plaster. Do not add any other substances into the mixture. 3. Support the formwork, then lay and fill in the plaster around
the cables and the bridges. Press compactly the cables into the
plaster to prevent any formation ofissures between the cables. 4. Fix a marking label, if necessary.on a visible location near the
fireproof sealing point. As identification for future maintenance. |